1 viewer
Solar · TX · being built
Tehuacana Creek Solar
A planning estimate from monthly means and the spread of days inside a month.
- Rated
- 645 MW
- A year
- 1,388 GWh
- Capacity factor
- 24.6%
Before it reports
- Owner
- Parliament Energy Holdings LLC
- Where
- Navarro County, TX
- Nameplate
- 645 MW in 1 generator
- Stage
- Under construction, more than half built
- Planned start
- May 2027
- Model, a whole year
- 1,388 GWh
- The inventory gives no array layout: taken as single-axis trackers, which most plants of this size are now built on.
- The inventory gives the inverter rating only: the modules are taken at 1.3 times it, about the utility-scale median.
- Crystalline silicon modules.
- Capacity, position, stage and start
- EIA-860M inventory of planned generators for September 2026, plant 65855
- Climate
- NASA POWER's monthly climatology at 31.9141, -96.4135
- Read
- 2026-11-11
The site
The plant
- Inverters
- 645 MW
- Modules
- 838 MW, Crystalline silicon
- Mount
- Single-axis trackers, north-south
- Light on level ground
- 1,728 kWh/m2 a year
- Light on the modules
- 2,173 kWh/m2 a year
- Yield
- 1,656 kWh a year per kW of modules
- Performance ratio
- 76.2%
- Lost at the inverter limit
- 0.0%
- Module area
- 408.9 ha
- Land at this ground cover
- 1,168.3 ha
- Losses taken
- 14.0%
Through the year
| Month | Clearness | Dull to clear day, kWh/m2 | Diffuse | On the modules kWh/m2 a day | Cell C | Clipped | Energy |
|---|---|---|---|---|---|---|---|
| Jan | 0.52 | 1.2 to 4.1 | 38.8% | 3.91 | 26 | 0.0% | 82.1 GWh |
| Feb | 0.48 | 1.2 to 5.0 | 47.9% | 4.11 | 29 | 0.0% | 77.7 GWh |
| Mar | 0.51 | 1.8 to 6.3 | 44.1% | 5.43 | 37 | 0.0% | 111.1 GWh |
| Apr | 0.54 | 2.4 to 7.5 | 42.1% | 6.65 | 43 | 0.0% | 128.9 GWh |
| May | 0.53 | 2.5 to 8.2 | 42.9% | 7.08 | 48 | 0.0% | 139.1 GWh |
| Jun | 0.58 | 3.3 to 8.7 | 38.0% | 8.17 | 53 | 0.0% | 151.8 GWh |
| Jul | 0.59 | 3.5 to 8.7 | 36.2% | 8.34 | 55 | 0.0% | 158.7 GWh |
| Aug | 0.59 | 3.3 to 8.0 | 36.1% | 7.85 | 56 | 0.0% | 148.9 GWh |
| Sep | 0.57 | 2.6 to 6.9 | 38.5% | 6.59 | 50 | 0.0% | 123.6 GWh |
| Oct | 0.57 | 2.1 to 5.6 | 38.5% | 5.48 | 42 | 0.0% | 109.2 GWh |
| Nov | 0.53 | 1.4 to 4.4 | 37.5% | 4.22 | 33 | 0.0% | 83.7 GWh |
| Dec | 0.50 | 1.0 to 3.8 | 40.8% | 3.49 | 27 | 0.0% | 73.1 GWh |
In 3D
To scale: 9 tracker rows 2.3 m wide, 6.6 m apart for a ground cover of 0.35, shown turned 35 degrees to the afternoon sun, on a 60 by 40 m patch of the 1168 ha site. 3D starts when Virtual's renderer loads.
What the model leaves out
- Each month is five kinds of day, from its dullest fifth to its clearest, at one air temperature. A day's light keeps a smooth shape: no cloud passes at noon, so clipping still reads a little low.
- Rows do not shade each other, and trackers do not backtrack.
- The sky's diffuse light is taken as even across the sky, which reads a little low for a tilted array under clear sky.
- Soiling, wiring, mismatch, ageing and outages are one share of output, the same in every month.
- Land is module area over ground cover. Roads, setbacks, the substation and unbuildable ground are extra.