1 viewer
Solar · NV · being built
Libra Solar
A planning estimate from monthly means and the spread of days inside a month.
- Rated
- 700 MW
- A year
- 1,904 GWh
- Capacity factor
- 31.1%
Before it reports
- Owner
- Libra Solar LLC
- Where
- Lyon County, NV
- Nameplate
- 700 MW in 1 generator
- Stage
- Under construction, half built or less
- Planned start
- Dec 2027
- Model, a whole year
- 1,904 GWh
- The inventory gives no array layout: taken as single-axis trackers, which most plants of this size are now built on.
- The inventory gives the inverter rating only: the modules are taken at 1.3 times it, about the utility-scale median.
- Crystalline silicon modules.
- Capacity, position, stage and start
- EIA-860M inventory of planned generators for September 2026, plant 69857
- Climate
- NASA POWER's monthly climatology at 38.9021, -118.9614
- Read
- 2026-11-11
The site
The plant
- Inverters
- 700 MW
- Modules
- 910 MW, Crystalline silicon
- Mount
- Single-axis trackers, north-south
- Light on level ground
- 1,960 kWh/m2 a year
- Light on the modules
- 2,711 kWh/m2 a year
- Yield
- 2,093 kWh a year per kW of modules
- Performance ratio
- 77.2%
- Lost at the inverter limit
- 0.1%
- Module area
- 443.9 ha
- Land at this ground cover
- 1,268.3 ha
- Losses taken
- 14.0%
Through the year
| Month | Clearness | Dull to clear day, kWh/m2 | Diffuse | On the modules kWh/m2 a day | Cell C | Clipped | Energy |
|---|---|---|---|---|---|---|---|
| Jan | 0.58 | 1.3 to 3.4 | 32.1% | 3.82 | 20 | 0.0% | 88.7 GWh |
| Feb | 0.61 | 2.0 to 4.6 | 29.5% | 5.20 | 24 | 0.0% | 108.1 GWh |
| Mar | 0.65 | 3.3 to 6.1 | 30.3% | 7.00 | 31 | 0.0% | 158.3 GWh |
| Apr | 0.67 | 4.4 to 7.7 | 28.6% | 8.80 | 36 | 0.0% | 189.4 GWh |
| May | 0.67 | 5.0 to 8.8 | 28.7% | 9.84 | 43 | 0.3% | 213.3 GWh |
| Jun | 0.72 | 6.2 to 9.5 | 24.5% | 11.22 | 50 | 0.6% | 227.6 GWh |
| Jul | 0.68 | 5.4 to 9.0 | 26.9% | 10.32 | 54 | 0.0% | 214.5 GWh |
| Aug | 0.71 | 5.3 to 8.3 | 25.4% | 9.81 | 52 | 0.0% | 205.0 GWh |
| Sep | 0.72 | 4.5 to 7.0 | 24.5% | 8.56 | 47 | 0.0% | 176.5 GWh |
| Oct | 0.70 | 3.3 to 5.2 | 25.7% | 6.55 | 36 | 0.0% | 144.7 GWh |
| Nov | 0.65 | 1.9 to 3.7 | 26.4% | 4.66 | 26 | 0.0% | 102.6 GWh |
| Dec | 0.55 | 1.0 to 3.0 | 35.7% | 3.25 | 18 | 0.0% | 75.7 GWh |
In 3D
To scale: 9 tracker rows 2.3 m wide, 6.6 m apart for a ground cover of 0.35, shown turned 35 degrees to the afternoon sun, on a 60 by 40 m patch of the 1268 ha site. 3D starts when Virtual's renderer loads.
What the model leaves out
- Each month is five kinds of day, from its dullest fifth to its clearest, at one air temperature. A day's light keeps a smooth shape: no cloud passes at noon, so clipping still reads a little low.
- Rows do not shade each other, and trackers do not backtrack.
- The sky's diffuse light is taken as even across the sky, which reads a little low for a tilted array under clear sky.
- Soiling, wiring, mismatch, ageing and outages are one share of output, the same in every month.
- Land is module area over ground cover. Roads, setbacks, the substation and unbuildable ground are extra.